Extended application of results from fire resistance tests for service installations - Part 2: Fire dampers
This European Standard provides guidance and rules to notified bodies (for fire dampers) to allow them to
produce/validate an extended field of application report for fire dampers. This standard identifies the
parameters that affect the fire resistance of dampers. It also identifies the factors that need to be considered
when deciding whether, or by how much, the parameter can be extended when contemplating the fire
resistance performance of an untested, or untestable variation in the construction.
This European Standard explains the principles behind how a conclusion on the influence of specific
parameters/constructional details relating to the relevant criteria (E,I,S) can be achieved.
This European Standard does not cover dampers used for smoke control.
This European Standard only applies to extended fields of application based on tests successfully undertaken
to EN 1366-2. Only test reports that have a total test time where the criteria are fulfilled that is in excess of the
required classification period by a margin of either 10 % or 12 min, whichever is the least, are to be
considered. Each classification (E,I,S) is to be considered individually – consequently E (134 min achieved)
may be extended, but EI (61 min achieved) may not be extended for a classification of EI60
ΚΩΔΙΚΟΣ ΠΡΟΪΟΝΤΟΣ:
CYS EN 15882-2:2015
This European Standard provides guidance and rules to notified bodies (for fire dampers) to allow them to
produce/validate an extended field of application report for fire dampers. This standard identifies the
parameters that affect the fire resistance of dampers. It also identifies the factors that need to be considered
when deciding whether, or by how much, the parameter can be extended when contemplating the fire
resistance performance of an untested, or untestable variation in the construction.
This European Standard explains the principles behind how a conclusion on the influence of specific
parameters/constructional details relating to the relevant criteria (E,I,S) can be achieved.
This European Standard does not cover dampers used for smoke control.
This European Standard only applies to extended fields of application based on tests successfully undertaken
to EN 1366-2. Only test reports that have a total test time where the criteria are fulfilled that is in excess of the
required classification period by a margin of either 10 % or 12 min, whichever is the least, are to be
considered. Each classification (E,I,S) is to be considered individually – consequently E (134 min achieved)
may be extended, but EI (61 min achieved) may not be extended for a classification of EI60